Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM04524
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/10/2006 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 08/10/2006 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 08/11/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM04524 8/11/06 THIS IS NOT A PLAN REVIEW, BUT RATHER A DOCUMENTATION OF CERTAIN ELEMENTS WHICH SHALL BE IN PLACE IN ORDER FOR REVIEW TO OCCUR. 1. The minimum font size is 1/8", all uppercase. 2. Electrical plans shall be prepared and sealed by a Registrant in the State of Arizona. |
| 08/11/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide listing information for the motorized filter fans showing that they are approved for use within a plenum. 2. Provide information to clarify the low sidewall returns (keynote 2, M-102), including grille sizes and balancing data. 3. The minimum font size is 1/8", all uppercase. |
| 08/11/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Provide a updated site plan. 2) Stamp drawing by a registrant in the state of Arizona. 3)Provide a completed code analysis - type of construction etc. 4) Provide building floor plan clarifying location of work. For exiting etc. 5) Provide wall section 6) Clarify rated cooridor? |
| 08/11/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/11/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 08/11/2006 | RSHERRY1 | WWM | REVIEW | Passed | |
| 08/11/2006 | DAVE MANN | FIRE | REVIEW | Approved | |
| 08/30/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |