Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM04508
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/19/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
09/19/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The revised drawing shows a 3" building drain. how many fixture units and how many water closets are being served by the 3" building drain? 2. The appeal to the building official must be approved prior to approval of the project. 3. The maximum hot water temperature to be supplied to a public lavatory is 110 degrees Fahrenheit. Reference Section 804.3, IECC 2003. |
09/19/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
09/19/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | Details provided |
10/02/2006 | GBONILL1 | WWM | REVIEW | Needs Review | |
10/02/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
10/02/2006 | GBONILL1 | FIRE | REVIEW | Needs Review |