Permit Number: T06CM04508
Parcel: 117061900

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM04508
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/19/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
09/19/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The revised drawing shows a 3" building drain. how many fixture units and how many water closets are being served by the 3" building drain?
2. The appeal to the building official must be approved prior to approval of the project.
3. The maximum hot water temperature to be supplied to a public lavatory is 110 degrees Fahrenheit. Reference Section 804.3, IECC 2003.
09/19/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
09/19/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved Details provided
10/02/2006 GBONILL1 WWM REVIEW Needs Review
10/02/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
10/02/2006 GBONILL1 FIRE REVIEW Needs Review