Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/08/2006 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
08/08/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show the location of the condensing unit, CU-1, on the plans and how it is to be mounted. 2. Show how ventilation is to be provided to the server room. Reference Section 403.3, IMC 2003. |
08/08/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM04488 8/8/06 1. Electrical load on Ckt 210-10,12 only accounts for CU-1. Please add AC-1 unless this is the published total for the entire split system. 2. Address overload protection for both CU-1 and AC-1. |
08/08/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
08/08/2006 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
08/08/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
08/08/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide information to show that the installation of the new sink complies with Section 707.4, UPC 2003. |
08/08/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
08/23/2006 | CAGUILA1 | WWM | REVIEW | Needs Review | |
08/23/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |