Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM04488
Parcel: 10821328B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM04488
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/08/2006 ANDREW CONNOR ZONING REVIEW Approved
08/08/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show the location of the condensing unit, CU-1, on the plans and how it is to be mounted.
2. Show how ventilation is to be provided to the server room. Reference Section 403.3, IMC 2003.
08/08/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM04488 8/8/06

1. Electrical load on Ckt 210-10,12 only accounts for CU-1. Please add AC-1 unless this is the published total for the entire split system.
2. Address overload protection for both CU-1 and AC-1.
08/08/2006 ROBERT SHERRY WATER REVIEW Approved
08/08/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
08/08/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
08/08/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide information to show that the installation of the new sink complies with Section 707.4, UPC 2003.
08/08/2006 MARTIN BROWN FIRE REVIEW Approved
08/23/2006 CAGUILA1 WWM REVIEW Needs Review
08/23/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review