Permit Number: T06CM04487
Parcel: 12615011C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM04487
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/08/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
08/08/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/08/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/08/2006 ROBERT SHERRY WATER REVIEW Approved
08/08/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
08/09/2006 TERRY STEVENS ZONING REVIEW Approved
08/09/2006 MARTIN BROWN FIRE REVIEW Approved
08/24/2006 GERRY KOZIOL WWM REVIEW Approved
08/24/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T06CM04487 8/8/06

1. Indicate which electrical circuit is intended for the new exit lights. Reference NEC 700.12 (E).
2. Phone system grounding conductor shall be connected to one of the options in NEC 800.40 (B).
3. Sheet A3 has a note addressing the event that the tenant provides panels with provisions for electrical power. Please modify this note to include the requirement that the panel and circuits for such power be identified, and that this be submitted with load calculations as a revision to the approved plans.
08/24/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed