Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM04487
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/08/2006 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
08/08/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
08/08/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
08/08/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
08/08/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
08/09/2006 | TERRY STEVENS | ZONING | REVIEW | Approved | |
08/09/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
08/24/2006 | GERRY KOZIOL | WWM | REVIEW | Approved | |
08/24/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T06CM04487 8/8/06 1. Indicate which electrical circuit is intended for the new exit lights. Reference NEC 700.12 (E). 2. Phone system grounding conductor shall be connected to one of the options in NEC 800.40 (B). 3. Sheet A3 has a note addressing the event that the tenant provides panels with provisions for electrical power. Please modify this note to include the requirement that the panel and circuits for such power be identified, and that this be submitted with load calculations as a revision to the approved plans. |
08/24/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |