Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. The following circuits have electrical load on Sheet E201, but are listed as spares on their respective panel schedules: B-25,27,29,31, F-18,20,22, F-37,39,41, C-39, C-6.
2. It appears that C-4 on the panel schedule represents incorrect loading. Please clarify.
3. F-2 and F-4 indicate Office 110 and Records 109 receptacles, respectively. Such circuits do not serve these areas on the Power Plan.
4. F-16 powers a receptacle on sheet E201, but is listed within Revision Cloud #4, which was already approved as Circuit F-16 on Revision 04 09/21/06 of the previously approved plans. Clarify for this circuit and for all others which may apply.
5. F-14,16 powers receptacle loads on sheet E201, but was listed within Revision Cloud #3 on the previously approved plans, where these circuits were powered from Circuit F-33,35. No revision cloud this submittal, even though this change has taken place. Clarify for this circuit and for all others which may apply.
6. On Sheet E301 no Revision Clouds for Revisions 7 and 8 appear on the plans. If no changes were made after City approval of this Sheet dated 12/15/06, please replace that approved sheet into the new set. No need to re-review, which would add to costs.
7. Reflect any changes as noted above on load calculations, as necessary.
03/29/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
04/18/2007 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/23/2007 BETH GRANT OUT TO CUSTOMER Completed