Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM04479
Parcel: 140420190

Address:
2701 E ELVIRA RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM04479
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics. Reference Section 103.2.3, UPC 2003.
2. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003.
3. Show upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks and urinals require cleanouts regardless of length). Reference Section 707.4, UPC 2003.
08/09/2006 ROBERT SHERRY WATER REVIEW Approved
08/09/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference Section 403.2.1, IMC 2003.
2. Clarify the number of water closets and urinals used in the ventilation calculations for this building; 15 are used in the calculations but only 14 are shown on the plans.
3. Clarify the smoke control plan for rooms 108,109, and 111 with regard to the non-protected transfer ducts.
4. Provide calculations to show that the corridor connecting the south building and the east building does not require fire separation.
5. Show how access to the rooftop equipment is to be provided. Reference Section 306.5, IMC 2003.
08/09/2006 BETSY COTTLE COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/10/2006 DAVE MANN FIRE REVIEW Approved
08/18/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Provide a maintenance receptacle for the new HP.
2. Account for existing load on Panel Schedule UPS2. Provide feeder size. On Load Summary, it appears that the additional load is 18.4 KVA, not 17.8.
3. Provide feeder size for panel D.
4. Account for existing load on Panel Schedule F. Provide feeder size for this panel.
5. Account for existing load on Panel Schedule PB1, including T2. Provide feeder size for this panel. Total on Load Summary would have a new load of 34.6 KVA, before accounting for the existing load on this panel. Load Summary only accounts for 21.3 KVA.
6. Provide feeder size for Panel A.
7. Provide feeder size for Panel B.
8. Provide feeder size for Panel C.
08/28/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .. T06CM04479 .. (2701) EAST ELVIRA ROAD .. REMODEL OFFICE FOR UNIVERSITY PHYSICIANS HEALTHCARE .. DGL .. IST REVIEW .. 9/5/06 ..

TRANSMIT PRIOR SUBMITTAL/S WITH NEXT SUBMITTAL.

Provide a Response Letter, by the Registrant of Record, with the re-submittal addressing each comment listed in Structural Review.

S1. Provide an Official Address Slip from Pima County Addressing to change the address of this building , as COT Records show the address of this building as 2721 East Elvira Road vs 2701 East Elvira Road listed on drawing #G0.03 and the Permit Application.
S2. It appears there is work intended for the north building, this will require an additional Permit Application and Code Review Checklist, as discussed in comment S1 above provide an Official Address Slip from Pima County Addressing as the address for this building for COT Records is 2701 East Elvia Road vs 2721 East Elvira Road shown on building ref drawing A2.03, verify all work is clearly shown.
S3. Provide completed Code Review Checklist, as required by 1997 Uniform Administrative Code Section 302.1, including: Job Address, Architect, Signature, Date, Summary of Governing Regulations, General Building Summary and Allowable Area Calculation for this building address. See DSD website : www.tucsonaz.gov/dsd, for form.
S4. Show location of conforming address signage, per Pima County Addressing Ordinance and IBC section 501.2 for this building, on the drawings.
S5. Provide Project Cost for the Permit for this building and show on drawing G0.01 an estimate explaining where 20% of the Project Cost for this building is spent on accessibility or the building is brought into conformance with the 2003 IBC Section 11 and 34 and ANSI A117.1-2003 ed.
S6. Provide revised drawing G0.02 showing accessibility fixture heights and locations conforming to Chapter 11 and 34 of the 2003 IBC and ANSI A117.1-2003 ed.
S7. . Detail on the drawings where conformance to the accessibility requirements of IBC Section 11 and 34 and ANSI A117.1-2003 ed are provided, showing how requirements are met and indicate Accessible Route.
S8. Indicate, on drawings, the existing Occupancy and Type of Construction for existing buildings on site, per IBC Sections 3 and 6, respectively, also indicate the Location, Type of and Fire-rating of existing Fire Walls on site, explaining if and how they are or are not to be maintained for the purposes of this Permit, per IBC Section 7.
S9. Clarify/revise drawing G0.04, this drawing has references in the Code Summary to the UBC, as the City of Tucson's current Building Code is the 2003 IBC update these references to the 2003 IBC and verify that the remainder of this design conforms to the 2003 IBC.
S10.Dimensionally locate, from two adjacent roof edges, new roof-mounted equipment on the Roof Plan drawing A1.11, including Sonotube Skylights and New Mechanical Unit.
S11. Clarify on drawing A4.02, Interior Finishes conformance with IBC Section 8, including Kraft Paper by listing Flame-spread and Smoke-development Wall and Ceiling Finishes per Section 803 and Table 803.5.
S12.Locate drinking fountain/s per IBC Section 29 and Table 2902.1, also address accessibility of drinking fountain/s, on drawing A1.02.
S13. Clarify how Means of Egress Illumination conforms to IBC Section 1006, ie: exterior exit lighting.
S14. Manual sliding doors do not appear to comply with IBC Section 1008, 1008.1.2 exc 5, 1008.1.1.3, provide complying sliding doors or revise drawing to conform.
S15. Clarify Exit Doors and Hardware conform to requirements of IBC Section 10 and 11:
1. Door #100.
2. Door #106.
3. Door #114A
4. Door #129.
5. Door #133.
Please comment.
S16. Provide Structural Calculations for :
1. Check existing roof structure capacity to support new ceiling, mechanical, electrical, fire sprinklers or other loads.
2. New canopy to replace existing at one location on this building.
S17. Provide Special Inspection for:
1. Field Welding.
2. Shop Welding.
3. Expansion Anchors.
4. Epoxy Anchors.


Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111, email at <Doug.Laakso@tucsonaz.gov.> or visit City of Tucson , DSD website : www.tucsonaz.gov/dsd.
09/06/2006 GERRY KOZIOL WWM REVIEW Denied needs 8th floor wastewater credit evaluation

Final Status

Task End Date Reviewer's Name Type of Review Description
09/13/2006 GERARDO BONILLA OUT TO CUSTOMER Completed
09/13/2006 SUE REEVES REJECT SHELF Completed