Permit Number: T06CM04470
Parcel: 11206424A

Address:
2545 N TUCSON BL

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM04470
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/07/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide information to show that the crematorium is listed per UL 791 and has been installed per the listing.
08/09/2006 HEATHER THRALL ZONING REVIEW Approved
08/09/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
08/09/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T06CM04470 8/7/06

1. The #2 conductor between Panel A and its disconnect is not of sufficient ampacity to be protected by the 200 AF.
08/10/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved