Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM04469
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/22/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM04469 9/22/06 Minimum font size is 1/8", Registrant shall sign and date seal, then bring in for review. |
| 09/22/2006 | ROBERT SHERRY | WATER | REVIEW | Passed | |
| 09/22/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003. 2. Clarify the piping modifications with a riser diagram. |
| 10/16/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 10/16/2006 | CAGUILA1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 10/16/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved |