Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM04469
Parcel: 115043500

Review Status: Completed

Review Details: OTHER

Permit Number - T06CM04469
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM04469 8/9/06

Identify panel and circuit for new receptacle, light, and exhaust fan.
08/09/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide an exhaust fan for the new restroom with a minimum flow of 75 CFM. Reference Section 403.3, IMC 2003.
08/09/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the plumbing plan to show the drain connection for the shower and provide water to the new water closet.
2. The length of the traparm for the lavatory in the new restroom is greater than the 3'-6" allowed for a 1-1/2" traparm.
3. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003.
09/22/2006 JMORALE1 WATER REVIEW Needs Review
09/22/2006 JMORALE1 BUILDING-COMMERCIAL REVIEW Needs Review
09/22/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/22/2006 JMORALE1 OUT TO CUSTOMER Completed