| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/09/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM04469 8/9/06 Identify panel and circuit for new receptacle, light, and exhaust fan. |
| 08/09/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide an exhaust fan for the new restroom with a minimum flow of 75 CFM. Reference Section 403.3, IMC 2003. |
| 08/09/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the plumbing plan to show the drain connection for the shower and provide water to the new water closet. 2. The length of the traparm for the lavatory in the new restroom is greater than the 3'-6" allowed for a 1-1/2" traparm. 3. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003. |
| 09/22/2006 | JMORALE1 | WATER | REVIEW | Needs Review | |
| 09/22/2006 | JMORALE1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 09/22/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/22/2006 | JMORALE1 | OUT TO CUSTOMER | Completed |