Permit Number: T06CM04445
Parcel: 126191190

Address:
824 S ERIN AV

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T06CM04445
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/01/2006 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS for Activity # T06CM04445

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2003 International Residential Code, 2003 International Energy Conservation Code, and Arizona State amendments to the 2003 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

As of 9-02-04 the City of Tucson has adopted the 2003 IRC with the exception of the plumbing portion which has been replaced with the 2003 UPC with amendments. All plans should reference these codes. See this site for all adopted amendments: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html

Provide sheet numbers on each drawings.

SITE PLAN:

1. Provide a note for: Underground facility tracer wires per DSD Memo, 10/24/2005.
2. Clarify if the 1" water pipe from the meter to the building is existing or replacing a ¾" pipe, 2003 UPC 610.1.

FOUNDATION PLANS:

1. Show a 24" square by 12" deep foundation at each load bearing post, R403.1, or redesign the roof assembly with a clear spanning structure.

FLOOR PLANS:

1. Show that each water closet is located in a clear space not less than 30" wide (centered 15" from finished wall or fixture) and has a clear space in front not less than 21", IRC figure R307.2.
2. Note that tub/shower enclosures shall have nonabsorbent surfaces to 6' above the floor, R307.2. All glass enclosures shall be tempered, R308.4.5.
3. Show the location of a minimum 22"X30" attic access. Attic access is required if the space exceeds 30SF with a minimum of 30" of headroom, and shall be located in a hallway or readily accessible space, R807.

STRUCTURAL PLANS:

1. Specify design criteria on plans. Provide values for floor dead load and live load as well as roof dead load and live load.
2. Specify lumber grade and species. Specify manufacturer and series on glue-lams and "I" joists.
3. Show masonry wall horizontal lateral support R606.8.1.
4. Note the top plate width consistent with the block width.
5. Specify steel lintels:
1' to 4' 2-3 ½"x3 ½" x ¼"
4' to 7' 2-4" x 3 ½" x 5/16"
7' to 9' 2-5" x 3 ½" x 5/16"
9' to 10' 2-5" x 3 ½" x 3/8"
10' to 12' 2- 6" x 4" x 3/8"
12' to 15' 2- 6" x 4" x 7/16"
15' to 18' 2- 8" x 4" x ½"
6. The 4"x 10" DF #1 beam over the Master Bedroom is undersized for a 13' span.
7. Show the ceiling joist size, or provide manufacturer's calculations and data for pre-fabricated trusses if used, R802.10.2, or note the requirement for deferred submittal approval prior to installation.
8. Specify the outrigger & gable end bracing and connections to the structure, R802.10.3.
9. Show details for typical non-bearing interior wall conditions (floor and rafter/joist connections & gaps).
10. Specify and detail all over-framing connections for intersecting pitched roof assemblies. Provide a minimum opening of 22" by 30" for access and ventilation between over-framed assemblies (>30 S.F.), R807.

SECTIONS - DETAILS - MISC. NOTES:

1. Indicate all materials used; interior framing for insulation cavity, wall board thickness etc.
2. Calculate the attic ventilation area using the correct attic area in compliance with R806.2. Note only 80% of the required ventilating area may be provided by ridge or gable vents when applying the reduced area calculation. Show the amount of eave vents needed to comply.
3. Show the ceiling gypsum board as either 5/8" or ½" sag resistant when applied to 24" o/c framing, IRC table R702.3.5 footnote d.
4. Show a minimum 1" ventilation clearance between ceiling insulation and roof sheathing if insulation is attached to truss bottom cords and eave venting is used, R806.3. This may be accomplished w/ baffles.

PLUMBING PLANS:

1. The City of Tucson has adopted the 2003 Uniform Plumbing Code with state amendments (ARIZONA STATE PLUMBING CODE). The plans should reference this code.
2. Note and specify all piping materials, UPC 301.1.1.
3. Provide the total fixture unit demand for the entire property per 2003 UPC Table 6-4,
including a dishwasher and ice maker if existing.
4. Provide pressure and temperature relief valve at water heater. T&P line must terminate at the exterior between 6 and 24 inches above grade and must terminate facing down, UPC 608.5.
5. Show an upper terminal cleanout at each horizontal drainage pipe greater than 5'(all drains with a sink) UPC 707.4.
6. Show the cleanout size (1-½" for drains up to 2" and 2-½" for drains up to 3") as required by Table 7-6. The water closet VTR may be used as the cleanout if increased to 2-½" or 3".

MECHANICAL PLANS:

1. Note on plans: Mechanical shall comply with 2003 IRC chapters 12 - 24.
2. Locate and show that the maximum length of dryer vent does not exceed 25' with consideration of bend reductions, M1501.3.
3. Show bathroom exhaust fan location (existing bathroom) with CFM rating R303.3 and M1506.

ELECTRICAL PLANS:

1. Note on plan that all electrical work shall comply with 2003 IRC chapters 33 - 42.
2. Provide a panel schedule showing panel size, circuit numbers, ampacity, wire size and general description for the new circuits, E3304.11 & E3606.2.
3. Show the size of the electrical panel, E3501.6.2.
4. Designate the circuit number at the location of each light fixture, receptacle, appliance and equipment disconnect switch, E3603.5.
5. Bathroom receptacles shall be on a separate 20 AMP circuit with no other outlets, E3603.4.
6. The receptacle serving the dryer should not be noted as GFCI. A 20 AMP branch circuit shall be installed to serve the laundry room (clothes washer) and this circuit shall have no other outlets, E3603.3 and 3801.8. GFCI not required.
7. Hallways of 10' or more in length require a receptacle, E3801.10.
8. Note that an arc-fault circuit interrupter shall protect bedroom outlets including receptacles, lights and smoke detectors, E3802.11.
9. Lights installed over a shower or bathtub must be approved for use in wet area, E3903.8.
10. Note that light fixtures in clothes closets shall be installed in accordance with E3903.11.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Tucson is in climate zone 4B, 2100 HDD, IRC chapter 11, local amendment. The simplified prescribed energy values for glazing U=0.65, ceiling R=19 and walls R=13 complies with 2003 IECC energy requirements, if glazing does not exceed 12% of exterior wall area. Show these values, or provide energy calculations per the 2003 IECC for compliance validations. Select the climate zone 4B, Pima County < 4000 ft, 2100 HDD if using REScheck. http://www.energycodes.gov/rescheck/ The solar heat gain coefficient SHGC should have a minimum value of 0.40.
2. Show the material used for achieving the wall R-value of insulation.

If you have any questions, please contact your assigned plans examiner Ken Van Karsen at 791-5550, extension 1112.
11/06/2006 GBONILL1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/06/2006 GERARDO BONILLA OUT TO CUSTOMER Completed