Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T06CM04439
Review Name: OTHER
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/11/2006 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | Specify the correct weight of unit lbs. or kgr. Plans show 133 lbs instead of kgrs. |
08/11/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
08/11/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Installation of the A/C units is to be per the manufacturer's instructions. The manufacturer calls for the condenser ducts to be installed but routing and termination of the ducts is the responsibility of the engineer and is to be shown on the plans. |