Permit Number: T06CM04439
Parcel: 12709012C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM04439
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/03/2006 HEATHER THRALL ZONING REVIEW Approved
08/03/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show how the condenser ducts for AC-1 are to be routed and terminated. Reference section 304.1, IMC 2003.
08/03/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
08/03/2006 ROBERT SHERRY WATER REVIEW Approved
08/03/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) Provide details showing how A/C unit is attached
at the top. Is it attached to a bm. truss, specify.
Provide calc`s.
08/03/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
08/03/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Specify the backflow device to be usedfor the coffee maker.
08/03/2006 MARTIN BROWN FIRE REVIEW Approved
08/11/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
08/21/2006 GERRY KOZIOL WWM REVIEW Approved