Review Details: COMMERCIAL TI
Permit Number - T06CM04439
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/03/2006 | HEATHER THRALL | ZONING | REVIEW | Approved | |
08/03/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show how the condenser ducts for AC-1 are to be routed and terminated. Reference section 304.1, IMC 2003. |
08/03/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
08/03/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
08/03/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Provide details showing how A/C unit is attached at the top. Is it attached to a bm. truss, specify. Provide calc`s. |
08/03/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
08/03/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Specify the backflow device to be usedfor the coffee maker. |
08/03/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
08/11/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
08/21/2006 | GERRY KOZIOL | WWM | REVIEW | Approved |