Permit Number: T06CM04430
Parcel: 11601013B

Review Status: Completed

Review Details: OTHER

Permit Number - T06CM04430
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/21/2006 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE DETAILS FOR NEW GYP BOARD SOFFIT FRAMING.

2) CLARIFY HOW CLEAR FLOOR SPACE AT NEW RESTROOM MEETS 48" REQUIREMENT PER 2003 ANSI A117. 1 FIG. 404.2.3.1 (f).

3) CLEAR FLOOR SPACE AROUND NEW WATER CLOSET DOES NOT APPEAR TO MEET 56" REQUIREMENT PER 2003 ANSI A117.1 SECTION 604.3.

4) PROVIDE DETAILS FOR MOUNTING OF GRAB BARS AND DISPENSERS PER SECTIONS 604.5 AND 604.7 OF ANSI 117.1.

5) DOOR SWING INTO NON-ACCESSIBLE WATER CLOSET COMPARTMENTS IS IMPEDED BY TOILETS.

6) SPECIFY HOW COMPLIANCE WITH 2003 IBC SECTIONS 1210.1 AND 1210.2 WILL BE MET (HARD NON-PERMEABLE SURFACES).

Final Status

Task End Date Reviewer's Name Type of Review Description
01/10/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
01/10/2007 SUE REEVES REJECT SHELF Completed