Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T06CM04430
Parcel: 11601013B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM04430
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/08/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/08/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
12/08/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/08/2006 JOHN WILLIAMS BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/08/2006 DELMA ROBEY OUT TO CUSTOMER Completed