Permit Number: T06CM04430
Parcel: 11601013B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM04430
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/12/2006 DAVE MANN FIRE REVIEW Approved
10/12/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the capacity of the restroom exhaust fans to comply with Section 403.3, IMC 2003 (the exhaust flow shall be equal to the air supply into the restroom or a minimum of 75 cfm per water closet or urinal, whichever is greater).
2. Show how the exhaust fans are to be operated to prevent recirculation of the air from the restrooms. Reference Section 403.2, IMC 2003.
10/12/2006 JWILLIA5 BUILDING-COMMERCIAL REVIEW Needs Review
10/12/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003.
2. Revise the size of the water supply to P3 (Urinal); ¾" piping will result in velocities that are in excess of 8 feet per second.
3. Clarify the extra water closet and lavatory shown on the right side of detail 4/A3.
4. Show the installation of the floor drains on the plumbing plans and risers. Provide specifications fpr the floor drains. Note that the floor shall slope toward the floor drains.
10/12/2006 HEATHER THRALL ZONING REVIEW Approved DDO - 06- 89 approved 09/27/06 and stamped per Frank P.
10/12/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM04430 10/12/06

Demonstrate compliance with the 2003 IECC for the 120 SF addition. The plans indicate that the lighting fixtures are 100W each. This would compute to 3.33 W/SF, which exceeds all values on Table 805.5.2. Identify Tenant area, and show computation.