Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T06CM04430
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/12/2006 | DAVE MANN | FIRE | REVIEW | Approved | |
| 10/12/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the capacity of the restroom exhaust fans to comply with Section 403.3, IMC 2003 (the exhaust flow shall be equal to the air supply into the restroom or a minimum of 75 cfm per water closet or urinal, whichever is greater). 2. Show how the exhaust fans are to be operated to prevent recirculation of the air from the restrooms. Reference Section 403.2, IMC 2003. |
| 10/12/2006 | JWILLIA5 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 10/12/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003. 2. Revise the size of the water supply to P3 (Urinal); ¾" piping will result in velocities that are in excess of 8 feet per second. 3. Clarify the extra water closet and lavatory shown on the right side of detail 4/A3. 4. Show the installation of the floor drains on the plumbing plans and risers. Provide specifications fpr the floor drains. Note that the floor shall slope toward the floor drains. |
| 10/12/2006 | HEATHER THRALL | ZONING | REVIEW | Approved | DDO - 06- 89 approved 09/27/06 and stamped per Frank P. |
| 10/12/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM04430 10/12/06 Demonstrate compliance with the 2003 IECC for the 120 SF addition. The plans indicate that the lighting fixtures are 100W each. This would compute to 3.33 W/SF, which exceeds all values on Table 805.5.2. Identify Tenant area, and show computation. |