Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM04430
Parcel: 11601013B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM04430
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM04430 8/2/06

1. Provide a lighting fixture schedule.
2. Identify panel and circuit numbers for all new electrical loads. Demonstrate that no feeder or branch circuit is overloaded.
3. Demonstrate compliance with the lighting power budget requirements of the 2003 IECC for new construction, and other area(s) constructed after 1994.
08/02/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide energy calculations for the addition to the building.
2. Revise the capacity of the restroom exhaust fans to comply with Section 403.3, IMC 2003.
3. Show how the exhaust fans are to be operated to prevent recirculation of the air from the restrooms. Reference Section 403.2, IMC 2003.
08/02/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the waste piping plan to comply with the requirements of the 2003 UPC. Show how the new piping relates to the existing piping.
2. Provide riser diagrams for the water supply and the waste piping.
3. Show the specifications and applicable standards for the fixtures being selected by the owner.
4. Show how the temperature of the water at the lavatories is to be limited to no more than 110 degrees Fahrenheit.
5. Show how the water piping has been sized and show that the additions do not overtax the existing water service.
6. The waste fixture units for this application shall be for assembly occupancy.
08/02/2006 ROBERT SHERRY WATER REVIEW Approved
08/02/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
10/12/2006 CAGUILA1 ZONING REVIEW Needs Review
10/12/2006 GERRY KOZIOL WWM REVIEW Approved
10/12/2006 CAGUILA1 BUILDING-COMMERCIAL REVIEW Needs Review
10/12/2006 CAGUILA1 FIRE REVIEW Needs Review
10/12/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved