Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM04387
Parcel: 117110990

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T06CM04387
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show the location and installation details of the hood exhaust fan. The manufacturer's literature indicates that the fan is to be located remote from the hood.
2. Show how the termination of the hood exhaust complies with Section 501.2.1, IMC
3. The electrical plan must be re-reviewed to resolve the panel conflicts prior to mechanical approval.
2003.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/08/2007 DELMA ROBEY APPROVAL SHELF Completed
03/08/2007 DELMA ROBEY OUT TO CUSTOMER Completed
03/08/2007 DELMA ROBEY REJECT SHELF Completed