Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show the location and installation details of the hood exhaust fan. The manufacturer's literature indicates that the fan is to be located remote from the hood.
2. Show how the termination of the hood exhaust complies with Section 501.2.1, IMC
3. The electrical plan must be re-reviewed to resolve the panel conflicts prior to mechanical approval.
2003.