Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T06CM04387
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/03/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show the location and installation details of the hood exhaust fan. The manufacturer's literature indicates that the fan is to be located remote from the hood. 2. Show how the termination of the hood exhaust complies with Section 501.2.1, IMC 3. The electrical plan must be re-reviewed to resolve the panel conflicts prior to mechanical approval. 2003. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/08/2007 | DELMA ROBEY | APPROVAL SHELF | Completed |
03/08/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
03/08/2007 | DELMA ROBEY | REJECT SHELF | Completed |