Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T06CM04387
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/18/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/18/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide balancing information for the revised area exhaust system. Show that the restroom exhaust outlets are complying with the requirements of Section 403.2.1, IMC 2003. 2. Show the location and installation details of the hood exhaust fan. 3. Show how the termination of the hood exhaust complies with Section 502.7.3.6, IMC 2003. 4. Show that adequate make-up air is being provided for the hood exhaust. Reference Section 501.3, IMC 2003. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/27/2006 | CINDY AGUILAR | APPROVAL SHELF | Completed |
| 12/27/2006 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |