Permit Number: T06CM04387
Parcel: 117110990

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T06CM04387
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/18/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
10/18/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide balancing information for the revised area exhaust system. Show that the restroom exhaust outlets are complying with the requirements of Section 403.2.1, IMC 2003.
2. Show the location and installation details of the hood exhaust fan.
3. Show how the termination of the hood exhaust complies with Section 502.7.3.6, IMC 2003.
4. Show that adequate make-up air is being provided for the hood exhaust. Reference Section 501.3, IMC 2003.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/27/2006 CINDY AGUILAR APPROVAL SHELF Completed
12/27/2006 CINDY AGUILAR OUT TO CUSTOMER Completed