Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM04387
Parcel: 117110990

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM04387
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/09/2006 ROBERT SHERRY WATER REVIEW Approved
08/09/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. A note in the corridor calls for an exhaust fan to be rebalanced to 1050 CFM. Provide information to show that this is possible.
2. Clarify revision 1 to sheet M1.0; is this supposed to be a make up air system?
3. Provide a complete design for the installation of the fume hood, including the installation details for the exhaust fan.
4. Provide calculations to show that the proposed exhaust fan has the capacity to properly exhaust the fume hood.
5. Full-size drawings are required.
08/15/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
08/15/2006 CAGUILA1 BUILDING-COMMERCIAL REVIEW Needs Review
08/15/2006 GERRY KOZIOL WWM REVIEW Passed
08/15/2006 CAGUILA1 ELECTRICAL-COMMERCIAL REVIEW Needs Review