Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T06CM04342
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/11/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations to show that the common ventilation system is sized in accordance with Section 403.3.2, IMC 2003. 2. Show the size, routing, and termination of the condensate drain for HP-27. Reference Section 307.2, IMC 2003 and Section 807.2, UPC 2003. 3. Show how the equipment is being installed. Reference Section 304.1, IMC 2003. 4. Show how adequate access is being provided for the equipment located on the roof. Reference Section 306.5, IMC 2003. |
| 04/11/2007 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE ORIGINAL STRUCTURAL CALCULATIONS COPIES ARE NOT READABLE. 2) CLARIFY EXISTING FRAMING MEMBERS WITH A FRAMING PLAN. 3) IT'S UNCLEAR FROM THE CALCULATION WHERE ALL THE LOADS ARE FROM THAT ARE BEING JUSTIFIED. |
| 04/19/2007 | CAGUILA1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/19/2007 | CINDY AGUILAR | APPROVAL SHELF | Completed |
| 04/19/2007 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |