Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T06CM04342
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/30/2006 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 11/30/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 11/30/2006 | DAVE MANN | FIRE | REVIEW | Approved | |
| 11/30/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Increase the exhaust air flow men's restroom; 75 CFM is required per water closet or urinal. |
| 11/30/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | Revision to electric and plumbing details - approved per Jason G. original approval 9/26/06 |
| 11/30/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The required number of fixture units for a single urinal is 20 when using Table 6-5, UPC 2003. Provide the analysis for the complete water system, include the size of the water meter and the water service pipe to the building. 2. The specified flush valve requires a 1" connection but the riser diagram shows a 3/4" branch size. |
| 12/05/2006 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 12/05/2006 | DROBEY1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | DELTA 5 REVISIONS OK |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/05/2006 | DELMA ROBEY | OUT TO CUSTOMER | Completed |