Review Details: REVISION - - 1ST

Permit Number - T06CM04342
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2006 HEATHER THRALL ZONING REVIEW Approved
11/30/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
11/30/2006 DAVE MANN FIRE REVIEW Approved
11/30/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Increase the exhaust air flow men's restroom; 75 CFM is required per water closet or urinal.
11/30/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved Revision to electric and plumbing details - approved per Jason G. original approval 9/26/06
11/30/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The required number of fixture units for a single urinal is 20 when using Table 6-5, UPC 2003. Provide the analysis for the complete water system, include the size of the water meter and the water service pipe to the building.
2. The specified flush valve requires a 1" connection but the riser diagram shows a 3/4" branch size.
12/05/2006 DROBEY1 WWM REVIEW Needs Review
12/05/2006 DROBEY1 BUILDING-COMMERCIAL REVIEW Needs Review DELTA 5 REVISIONS OK