Review Details: COMMERCIAL TI
Permit Number - T06CM04342
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/02/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the drawing as required to show that the new location for the two heat pumps (and the existing condensing unit) provides adequate clearance for maintenance and operation. The current drawing indicates impossible installation configurations for the proposed equipment. |
| 08/10/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 08/10/2006 | GBONILL1 | WWM | REVIEW | Needs Review | |
| 08/10/2006 | GBONILL1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 08/10/2006 | GBONILL1 | ENGINEERING | REVIEW | Needs Review |