Permit Number: T06CM04342
Parcel: 12905401D

Address:
2055 E 19TH ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM04342
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/01/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/01/2006 MARTIN BROWN FIRE REVIEW Approved No storage above 12'-0" AFF
08/01/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide information to show that the new location for the two heat pumps (and the existing condensing unit) provides adequate clearance for maintenance and operation.
2. Provide the operating parameters for the unlabeled
exhaust fans shown in the new restrooms. Clarify the condition of the exhaust fans - they are shown as new on the electrical plans.
08/02/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
08/02/2006 JMORALE1 BUILDING-COMMERCIAL REVIEW Needs Review
08/02/2006 JMORALE1 ENGINEERING REVIEW Needs Review
08/02/2006 JMORALE1 WWM REVIEW Needs Review