Review Date Reviewer's Name Type of Review Description Status Comments
07/26/2006 HEATHER THRALL ZONING REVIEW Denied 2055 e 19th street
Stewart Wholesale

Reviewer: David Rivera
Principal Planner
August 11, 2006

The following items must be addressed:

1. A Pima County Parcel Tax code combo is required including a recorded COT Lot Combo Covenant. Mandy has been provided both documents.

Change all relevant information or code data on the plans to reflect the proposed use from Retail to Wholesale. Include Land Use Code data and notes associated to the Wholesale Use.

2. Site requirements include

a. Re-striping of the parking lot parking spaces to match the previously approved site plan.

b. C of O application must be for a Wholesale use instead of a Retail use.

c. FYI: By applying for a Wholesale use C of O, the site cannot be re-approved in the future as a retail use without meeting code comopliance in affect at the time of application. Board of adjustment variances may be required.

All non-conforming status for the use as retail will be lost.
07/26/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide details and structural calculations to show that the relocated fan coi3. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units. Reference Section 302.1, IMC 2003.
2. Provide the operating parameters for the unlabeled exhaust fans shown in the new restrooms.
3. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units. Show how they are to be mounted on the roof. Reference Section 302.1, IMC 2003.
07/26/2006 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
07/26/2006 ROBERT SHERRY WATER REVIEW Approved
07/26/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show the size of the building drain after 3" section from the new restrooms connects to the section from the existing drains.
2. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003.
08/01/2006 GBONILL1 WWM REVIEW Needs Review
08/01/2006 GBONILL1 BUILDING-COMMERCIAL REVIEW Needs Review
08/01/2006 GBONILL1 ENGINEERING REVIEW Denied
08/01/2006 GBONILL1 FIRE REVIEW Needs Review
08/01/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review