Permit Number: T06CM04339
Parcel: 105097280

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T06CM04339
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/13/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
2. The civil drawings referenced on sheet P1 are not included in the drawing set. Provide site drawing showing the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. Reference Section 103.2.3, UPC 2003.
3. The civil drawings referenced on sheet P1 are not included in the drawing set. Provide site drawing showing the size, route, and slope of the building sewer. Reference Section 103.2.3, UPC 2003.
09/13/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
09/29/2006 EGRANT1 BUILDING-COMMERCIAL REVIEW Needs Review
09/29/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
09/29/2006 EGRANT1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/29/2006 BETH GRANT OUT TO CUSTOMER Completed