Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T06CM04254
Parcel: 125010880

Address:
2915 E 5TH ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T06CM04254
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2006 GERRY KOZIOL WWM REVIEW Approved
08/21/2006 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS for Activity # T06CM04254

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2003 International Residential Code, 2003 International Energy Conservation Code, and Arizona State amendments to the 2003 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.


Provide a note for: Underground facility tracer wires per DSD Memo, 10/24/2005.


SITE PLAN:

1. Indicate the location of gas, water, electric and sewer or septic line on the property, from property line to building. Provide the location of utility meters.
2. Show the water pipe size from the meter to the building. The pipe must be sized for the calculated load, 2003 UPC 610.1.

FOUNDATION PLANS:

1. Revise Section A/2 showing a 6" minimum separation of untreated exterior posts above finished grade, R319.1.4.
2. Detail the foundation for the load-bearing wall in the carport area.
3. Show under-floor space ventilation. Openings shall be not less than 1 SF for each 150 SF of area, R408.2.
4. Show the location of a minimum 18"X24" access to under floor space that exceeds 30SF, R408.3.

STRUCTURAL PLANS:

1. Revise design criteria on plans. Change framing Note #14, sheet 7, to 40 psf for the Floor Live Load, Table R301.5
2. Show the LPI series on the Floor and Roof Framing Plans, sheet 5 & 6. Some series will not span the required 17.5'.
3. Show the roof slope for the carport area.

SECTIONS - DETAILS - MISC. NOTES:

1. Show the ceiling gypsum board as either 5/8" or ½" sag resistant when applied to 24" o/c framing, IRC table R702.3.5 footnote d.

ELECTRICAL PLANS:

1. Designate the circuit number at the bedroom exterior light fixture, E3603.5. This circuit requires arc-fault circuit interrupter protection, E3802.11.
2. Note that at least one 20 AMP branch circuit shall be installed to serve the laundry room and this circuit shall have no other outlets, E3603.3 and 3801.8.
3. Hallways of 10' or more in length require a receptacle, E3801.10.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Correct the Energy Values shown on the Floor Plan sheet 1. Provide the simplified prescribed energy values for glazing U=0.65, ceiling R=30 and walls R=13 when glazing does not exceed 15% of exterior wall area, or provide energy calculations per the 2003 IECC w/ local amendments for compliance validations. If using REScheck select the climate zone 4B, Pima County < 4000 ft, 2100 HDD on the web version. http://www.energycodes.gov/rescheck/
2. Revise General Note #11, sheet 7 referencing the 2003 International Energy Conservation Code.
3. Show the "R" values of insulation, as well as the "U" values of the windows and doors on the plans as well as the solar heat gain coefficient SHGC minimum value of 0.40 rather than the previously accepted MEC values.

If you have any questions, please contact your assigned plans examiner Ken Van Karsen at 791-5550, extension 1112.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/07/2006 GERARDO BONILLA OUT TO CUSTOMER Completed
09/07/2006 SUE REEVES REJECT SHELF Completed