Permit Number - T06CM04235
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/19/2006 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 07/19/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T06CM04235 7/19/06 1. Provide the grounding required at Second Building per NEC 250.32 (B) (1). 2. Provide the Disconnecting Means required at trailer per NEC 225.31. Panel schedule does not indicate MLO or MCB. |
| 07/25/2006 | MICHAEL ST. PAUL | ZONING | REVIEW | Passed | |
| 08/01/2006 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 08/01/2006 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Passed |