Permit Number: T06CM04235
Parcel: 11918036A

Address:
602 W AJO WY

Review Status: Completed

Review Details: OTHER

Permit Number - T06CM04235
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2006 JASON GREEN ENGINEERING REVIEW Approved
07/19/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T06CM04235 7/19/06

1. Provide the grounding required at Second Building per NEC 250.32 (B) (1).
2. Provide the Disconnecting Means required at trailer per NEC 225.31. Panel schedule does not indicate MLO or MCB.
07/25/2006 MICHAEL ST. PAUL ZONING REVIEW Passed
08/01/2006 GERRY KOZIOL WWM REVIEW Passed
08/01/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Passed