Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2006 LOREN MAKUS ENGINEERING REVIEW Approved
07/19/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T06CM04234 7/19/06

1. Provide the grounding required at Second Building per NEC 250.32 (B) (1).
2. Provide the Disconnecting Means required at trailer per NEC 225.31. Panel schedule does not indicate MLO or MCB.
3. Provide load calculations for 200A panel and service.
07/25/2006 MICHAEL ST. PAUL ZONING REVIEW Approved
08/01/2006 GERRY KOZIOL WWM REVIEW Completed
08/01/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Passed