Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T06CM04234
Review Name: OTHER
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/19/2006 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
07/19/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T06CM04234 7/19/06 1. Provide the grounding required at Second Building per NEC 250.32 (B) (1). 2. Provide the Disconnecting Means required at trailer per NEC 225.31. Panel schedule does not indicate MLO or MCB. 3. Provide load calculations for 200A panel and service. |
07/25/2006 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
08/01/2006 | GERRY KOZIOL | WWM | REVIEW | Completed | |
08/01/2006 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Passed |