Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T06CM04211
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/25/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 10/25/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The applicable code for all commercial plumbing projects is the 2003 Uniform Plumbing Code with Local Amendments. (See the Code Analysis Data on sheet CS-01.) 2. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. This applies to all submitted drawings. 3. The flow control device shall be installed so that it is visible, readily accessible, and per the manufacturer's listing information. For the specified Zurn flow control device, "The flow control device should be installed in the waste line upstream of the grease interceptor. It should be placed beyond the last connection from the fixture(s) and as close as possible to the underside of the lowest fixture." |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/26/2006 | VFLORES1 | APPROVAL SHELF | Completed |
| 10/26/2006 | VFLORES1 | OUT TO CUSTOMER | Completed |
| 10/26/2006 | GERARDO BONILLA | REJECT SHELF | Completed |