Permit Number: T06CM04211
Parcel: 13809008A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM04211
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/25/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/25/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The applicable code for all commercial plumbing projects is the 2003 Uniform Plumbing Code with Local Amendments. (See the Code Analysis Data on sheet CS-01.)
2. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. This applies to all submitted drawings.
3. The flow control device shall be installed so that it is visible, readily accessible, and per the manufacturer's listing information. For the specified Zurn flow control device, "The flow control device should be installed in the waste line upstream of the grease interceptor. It should be placed beyond the last connection from the fixture(s) and as close as possible to the underside of the lowest fixture."