Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM04211
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/18/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/19/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/19/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 07/20/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The applicable code for all commercial plumbing projects is the 2003 Uniform Plumbing Code with Local Amendments. 2. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 3. Complete the waste and vent isometrics by adding the missing pipe sizes. Reference Section 103.2.3, UPC 2003. 4. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003. 5. Appliances (e.g. ovens, ice makers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Table 6-3, UPC 2003 require backflow prevention. Reference Sections 602.3, 603.0, and Table 6-2, UPC 2003. 6. Resize the vent piping to conform to Table 7-5, UPC 2003 (e.g. no more than 8 waste fixture units on a 1-1/2" vent). Reference Section 703.2, UPC 2003 7. Provide a vent to protect the grease trap from siphonage and backpressure. Reference Section 1002.1, UPC 2003. 8. The trap and trap arm for a lavatory may not be increased more than one size larger than the minimum trap size shown in Table 7-3. With a 1-1/2" trap arm, the lavatories are located too far from the waste stack of the water closet to be wet-vented as shown. (Note: the waste stack for the water closet does not have to be directly behind the water closet.) Reference Sections 1002.2 and 1003.3, UPC 1994. 9. The flow control device for a grease trap shall be installed in a location that is readily accessible and visible. Reference Section 1014.3, UPC 2003. UPC 2003. |
| 07/20/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 2. Show the sizes for the condensate drains for the walk-in cooler and freezer. Reference Sections 106.3.1 and 307.2.2, IMC 2003, as amended by the City of Tucson. 3. Provide information to show how the condensate drains for the roof top units have been sized. Reference Section 307.2.2, IMC 2003, as amended by the City of Tucson. 4. Provide information on the sequence of operation for the restroom exhaust fans to show that recirculation of the air from the restrooms will not occur. Reference Section 403.2.1, IMC 2003. |
| 07/28/2006 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/09/2006 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 08/24/2006 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/31/2006 | JMORALE1 | OUT TO CUSTOMER | Completed |
| 08/31/2006 | SUE REEVES | REJECT SHELF | Completed |