Permit Number: T06CM04197
Parcel: 129010360

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T06CM04197
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/24/2006 DAVE MANN FIRE REVIEW Approved
10/27/2006 HEATHER THRALL ZONING HC SITE REVIEW Approved
10/27/2006 HEATHER THRALL ZONING REVIEW Approved
11/03/2006 ANDREW CONNOR NPPO REVIEW Approved
11/03/2006 ANDREW CONNOR LANDSCAPE REVIEW Approved
11/28/2006 SUZANNE BOHNET ENGINEERING REVIEW Denied To: Brian McCarthy, AIA
McCarthy Architecture, Inc.
DATE: November 30, 2006
FROM: Suzanne Bohnet, CFM
Engineering Division

SUBJECT: 300 S. Tucson Blvd.
Tenant Improvements: Church
Site Plan T06CM04197 (Second Review)

RESUBMITTAL REQUIRED: Site Plan.

The Site Plan cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:
1. Please provide the sight visibility triangle (SVT) for the intersection of Tucson Blvd. and Parkway Terrace as shown by redline.

2. Please clarify why the near-side and far-side SVT on the drive are not measured from the same point. The near-side is measured from face-of-curb and the far-side is measure 9' from face-of-curb.

3. Curb access ramps are required at all points where a sidewalk intersects a curb (D.S. 3-01.3.3.C). Truncated domes are required on all curb access ramps where the interface of the pavement or vehicle use area and the pedestrian area do not have a vertical separation. The area where the truncated domes are required is 6 inches back from the interface, a minimum 2 feet deep and extending the width of the interface. Please see redline for specific locations.

4. Please provide the dimensions from the centerline of Tucson Blvd. to the edge of curb and the edge of sidewalk.

Please do not hesitate to contact me with any questions.

Thank you,
Suzanne Bohnet, CFM
Engineering Associate
(520) 791-5550 x1188 office
Suzanne.Bohnet@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
12/01/2006 FSANCHE1 OUT TO CUSTOMER Completed