Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM04186
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/17/2006 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 07/17/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide structural details and material specifications for the "approved manner" of mounting the water heater to the wall along with the construction details for the wall to which the water heater is to be mounted. 2. Coordinate the electrical requirements for the water heater (i.e. 208V versus 240V). |
| 07/17/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
| 07/17/2006 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 07/17/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide ventilation for the office. 2. Provide ventilation for the shower room. 3. Provide information to show that no recirculation the air supplied to the restroom will occur. |
| 07/17/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/18/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/18/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM04186 7/18/06 1. New Water Heater is specified for 240V on Sheet P1.1. Electrical provides 208V power. Coordinate with Plumbing and clarify. 2. Mechanical calls for exhaust fans in the Restroom and Shower. Electrical powers only one EF. Coordinate with Mechanical and clarify. 3. Show the Water Heater circuit on Power Plan. |
| 07/24/2006 | DAVE MANN | FIRE | REVIEW | Approved | |
| 07/24/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |