Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T06CM04186
Parcel: 141153540

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM04186
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/17/2006 MICHAEL ST. PAUL ZONING REVIEW Approved
07/17/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide ventilation for the office.
2. Provide ventilation for the shower room.
3. Provide information to show that no recirculation the air supplied to the restroom will occur.
07/17/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide structural details and material specifications for the "approved manner" of mounting the water heater to the wall along with the construction details for the wall to which the water heater is to be mounted.
2. Coordinate the electrical requirements for the water heater (i.e. 208V versus 240V).
07/17/2006 ROBERT SHERRY WATER REVIEW Approved
07/17/2006 GERRY KOZIOL WWM REVIEW Approved
07/17/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
07/18/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
07/18/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM04186 7/18/06

1. New Water Heater is specified for 240V on Sheet P1.1. Electrical provides 208V power. Coordinate with Plumbing and clarify.
2. Mechanical calls for exhaust fans in the Restroom and Shower. Electrical powers only one EF. Coordinate with Mechanical and clarify.
3. Show the Water Heater circuit on Power Plan.
07/24/2006 DAVE MANN FIRE REVIEW Approved
07/24/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review