Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM04127
Parcel: 113052570

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM04127
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/05/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1)PROVIDE A BREAKDOWN OF EXPENDITURES ON 20% COST OF CONSTRUCTION BEING SPENT TOWARDS ACCESSIBILITY. SECTION 3409.6 EXCEPTION 1.
2) MODIFY FLOOR PLAN TO COMPLY WITH DOOR ENCROACHMENT 1005.2.
3) PROVIDE ACCESSIBLE RESTROOMS PER ANSI A117.1 2003.
4) CLARIFY THAT BREAKROOM IS FULLY COMPLIANT WITH ANSIA117.1 2003.
5) ACCESSIBLE ROUTE PER SECTION 403.5.
09/05/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/05/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
09/05/2006 ROBERT SHERRY WATER REVIEW Approved
09/15/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved t06cm04127 9/5/06

1. Provide power for RCP-1. Reference Sheet P2.0.
2. Account for replacement HPs on Electrical Drawings. Verify size of disconnecting means, conductors, and overcurrent protection.
3. Indicate exact location of electrical service. Electrical Plans Examiner will then determine if available fault current is an issue.
4. Specify the series rating of the line side overcurrent protective device for Panel A.
5. Since the overcurrent protective device to Panel Z and its branch circuit breakers are to be powered from Panel A, address fault current at Panel Z. Indicate whether this panel is MLO or MCB.
09/20/2006 JMORALE1 WWM REVIEW Needs Review
09/20/2006 STEVE SHIELDS ZONING REVIEW Approved
09/20/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
09/20/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
09/20/2006 MARTIN BROWN FIRE REVIEW Approved