Review Details: REVISION - - 1ST
Permit Number - T06CM04118
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/28/2007 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 02/28/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 03/01/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | DELTA 1 REVISION ONLY |
| 03/01/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM04118 3/1/07 1. Provide power requirements for all new lighting fixtures. 2. Electrical Plan indicates receptacles on Ckt 2. This is a spare on the Panel Schedule. 3. Electrical Plan indicates receptacles on Ckt 3. This is a space on the Panel Schedule. 4. Electrical Plan indicates receptacles on Ckt 1. This is a spare on the Panel Schedule. 5. The consideration of 1500VA for appliance circuits is only applicable to residential load calculations. This is commercial. 6. The consideration of 3 VA is not applicable to lighting in office spaces. See NEC Table 220.3 (A). 7. The application of the 40% demand factor is only applicable to residential occupancies per NEC 220.30. Review NEC Article 220. 8. All work on this sheet shall be minimum font size 1/8". |