Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2007 STEVE SHIELDS ZONING REVIEW Approved
02/28/2007 PATRICIA GILBERT ENGINEERING REVIEW Approved
03/01/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved DELTA 1 REVISION ONLY
03/01/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM04118 3/1/07

1. Provide power requirements for all new lighting fixtures.
2. Electrical Plan indicates receptacles on Ckt 2. This is a spare on the Panel Schedule.
3. Electrical Plan indicates receptacles on Ckt 3. This is a space on the Panel Schedule.
4. Electrical Plan indicates receptacles on Ckt 1. This is a spare on the Panel Schedule.
5. The consideration of 1500VA for appliance circuits is only applicable to residential load calculations. This is commercial.
6. The consideration of 3 VA is not applicable to lighting in office spaces. See NEC Table 220.3 (A).
7. The application of the 40% demand factor is only applicable to residential occupancies per NEC 220.30. Review NEC Article 220.
8. All work on this sheet shall be minimum font size 1/8".