Permit Number: T06CM04110
Parcel: 10702017A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM04110
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/14/2006 DAVE MANN FIRE REVIEW Denied Structure appears to be open and closer than 10' to property line. Clarify structure satisfies seperation requirements of 2003 IBC.
08/03/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied 1) Sheet RS-1, under building code review, allowable
increase front, the ratio of W/30 in the formula shall
not exceed 1.
08/14/2006 BETSY COTTLE COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed impact fees are due but need confirmation of sf of 2360
08/14/2006 BETSY COTTLE COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed Central District
2360 sf
$1902.64
09/05/2006 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: BORDER PRODUCTS - 3143 N. Freeway Industrial Loop
T06CM04110
Site Plan (1st Review)


TRANSMITTAL DATE: September 5, 2006

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site plan with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please call Steve Shields,
(520) 791-5608 ext. 1180.


RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents