Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T06CM04093
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/29/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | 2/22/08 T08CM04093 1. #6 feeder to Sub-Panel B is not protected by the 100A circuit breaker in Sub-Panel A. Correct here and all others which may apply. 2. Please show the circuit breaker protecting Sub-Panel MGR. Correct here and all others which may apply. 3. Panel B calculations show total amperage of 231A on a 200A panel. Rework panel and feeder load calculations taking into account 25% for largest motor and for continuous loads for all levels of the system. Put panel schedules on the plans. |