Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T06CM04093
Parcel: 10705148A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM04093
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/29/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved 2/22/08 T08CM04093

1. #6 feeder to Sub-Panel B is not protected by the 100A circuit breaker in Sub-Panel A. Correct here and all others which may apply.
2. Please show the circuit breaker protecting Sub-Panel MGR. Correct here and all others which may apply.
3. Panel B calculations show total amperage of 231A on a 200A panel. Rework panel and feeder load calculations taking into account 25% for largest motor and for continuous loads for all levels of the system. Put panel schedules on the plans.