Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM04093
Parcel: 10705148A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM04093
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/19/2008 STEVE SHIELDS ZONING REVIEW Approved
02/20/2008 RONALD BROWN 2ND PARTY REVIEW REVIEW Approved
02/20/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/20/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

1. Reference Note 1A, replacement receptacles shall comply with NEC 406.3 (D).
2. Reference Notes 1I and 1K, please perform this field check before submitting to design. Document any changes to electrical loads, conductor, and circuit breakers on the plans.
3. Provide an electrical circuit for the A/C-Heater units.
4. Provide an electrical outlet for the A/C-Heater units.
5. Provide panel and service load calculations for the A/C-Heater units, using a Code-compliant methodology. See NEC Article 220.
6. Load calculations indicate 50%. Justify this comment per NEC Article 220.
7. Load calculations account for 5A on AC/HT Pump. Cut sheet has 12A.
8. Load calculations count 10 units. Plans have 20 units.