Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T06CM04093
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/19/2008 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 02/20/2008 | RONALD BROWN | 2ND PARTY REVIEW | REVIEW | Approved | |
| 02/20/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 02/20/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. 1. Reference Note 1A, replacement receptacles shall comply with NEC 406.3 (D). 2. Reference Notes 1I and 1K, please perform this field check before submitting to design. Document any changes to electrical loads, conductor, and circuit breakers on the plans. 3. Provide an electrical circuit for the A/C-Heater units. 4. Provide an electrical outlet for the A/C-Heater units. 5. Provide panel and service load calculations for the A/C-Heater units, using a Code-compliant methodology. See NEC Article 220. 6. Load calculations indicate 50%. Justify this comment per NEC Article 220. 7. Load calculations account for 5A on AC/HT Pump. Cut sheet has 12A. 8. Load calculations count 10 units. Plans have 20 units. |