Permit Number: T06CM04079
Parcel: 133243690

Address:
100 N PANTANO RD

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T06CM04079
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/14/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/14/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
05/14/2015 MARTIN BROWN FIRE REVIEW Approved
05/15/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following dicrepencies:
#1. As per general note 'A' Plan Sheet 'E2', per plan scale, some of the lighting track exceeds 32 linear feet per circuit. Also the 4 'D' luminaires at column H-5.1 have no circuit designation.
#2. Please assign homerun circuit, panel for receptacles on Plan Sheet 'E3' at columns 5.1- D- thru- G.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/20/2015 KROBLES1 OUT TO CUSTOMER Completed