Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T06CM04079
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/14/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/14/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 05/14/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/15/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following dicrepencies: #1. As per general note 'A' Plan Sheet 'E2', per plan scale, some of the lighting track exceeds 32 linear feet per circuit. Also the 4 'D' luminaires at column H-5.1 have no circuit designation. #2. Please assign homerun circuit, panel for receptacles on Plan Sheet 'E3' at columns 5.1- D- thru- G. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/20/2015 | KROBLES1 | OUT TO CUSTOMER | Completed |