Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM04035
Parcel: 108252400

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T06CM04035
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/26/2010 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 4-26-10
Activity: T06CM04035
Address: 2399 E Blue Diamond Dr
Applicant: A.F. Sterling

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
2. Any architect and/or engineer involved in the design of the structure shall seal the related sheets of plans including revisions, details and calculations in accordance with the rules of the State Board of Technical Registration.

PLUMBING PLAN:
3. Appendix L calculations are only permissible for master meter applications per Tucson Water. Provide calculations based on appendix A of the 2006 UPC.
4. A 5/8" water meter does not meet the minimum design criteria for the proposed application. Provide a 1" water meter.
5. Provide backflow prevention for buildings three or more stories in height per Tucson Water.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review
04/26/2010 CLAYTON TREVILLYAN PLUMBING-COMMERCIAL REVIEW Denied SEE RESIDENTIAL COMMENTS

Final Status

Task End Date Reviewer's Name Type of Review Description
04/27/2010 GERARDO BONILLA OUT TO CUSTOMER Completed
04/27/2010 SUE REEVES REJECT SHELF Completed