| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/06/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/06/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | A) Please add the following automatic sprinkler criteria to the plans: 1. The hazard classification of the occupancy, including any special hazards. 2. The design standard to be used. 3. The availability and adequacy of the water supply. 4. The design density and the area of operation B. Indicate quantities of any hazardous materials to be stored and include MSDS. C. There appears to be racks in the Storage area. Please indicate height of racks and any other relevant information regarding methods of storing on racks. |
| 11/08/2006 | KAROL ARAGONEZ | ZONING | REVIEW | Approved | |
| 11/13/2006 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 11/13/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | Submit the approved site plan with the building plan. Once the set is together, the building plan can be approved. Please be advised building plan approval can occur over the counter with the approved site plan. |
| 11/13/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | Approved Site Plan submitted with Building plans. |