Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM03985
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/07/2006 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/07/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 07/07/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/07/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/07/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 07/07/2006 | RSHERRY1 | WWM | REVIEW | Passed | |
| 07/10/2006 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 07/10/2006 | PATRICIA GILBERT | ENGINEERING | REVIEW | Needs Review | |
| 07/10/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 07/10/2006 | MARTIN BROWN | FIRE | REVIEW | Approved |