Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2006 ADRIAN ALEGRIA BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS for Activity # T06CM03947

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2003 International Residential Code, 2003 International Energy Conservation Code, and Arizona State amendments to the 2003 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

Two set of complete plans, a minimum plan size of 24"x 36" and a maximum plan size of 30"x 42". No loose sheets shall be attached, but structural calculations and manufactures cut sheets may accompany plans. The plans shall be drawn to scale of ¼"=1' and indicate the drawing scale.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

Construction drawing guidelines are available from the residential desk of the Development Services Division.

List the square footages for all the following areas separately on the drawings:
- Livable area
- Garage
- Porch/Patio covers
- Decks

As of 9-02-04 the City of Tucson has adopted the 2003 IRC with the exception of the plumbing portion which has been replaced with the 2003 UPC with amendments. All model plans shall reference these codes.
All code references to the International Residential Code shall be changed from 2000 to 2003 with appropriate paragraph references.
Provide a note for: Underground facility tracer wires per DSD Memo, 10/24/2005.

SITE PLAN:

· Show the water pipe size from the meter to the building. The pipe must be sized for the calculated load, 2003 UPC 610.1.

FOUNDATION PLANS:

· Locate and detail all footings for the following:
girder truss bearing locations
turndowns
interior bearing walls
posts or columns
· Provide detail for foundation connection with the existing foundation. At least #4 dim. 6" long min. rebar embedded each side @ 48" max O.C. full length set in epoxy.
· Show or note a 6" minimum separation of untreated exterior posts above finished grade, R319.1.4.
· Dimension the wall thickness, footing width thickness and depth into undisturbed soil for each footing type and condition, IRC table R403.1.
· Minimum footing width required for one story construction, IRC table R403.1:
12" minimum for wood frame
12" minimum for hollow concrete / masonry
16" minimum for solid fully grouted masonry
· Show the minimum 12" footing depth below undisturbed soil, R403.1.4.
· Note and detail minimum reinforcing, or provide code justification for alternate.
For monolithic - one (1) #5 or two (2) #4 re-bars in the middle of the footing, R403.1.3.2.
For stem-wall - one (1) #4 re-bar in the bottom of the footing and one (1) #4 re-bar in the top of the stem.
For braced walls, IRC section R602.10.6.
For stem-wall with unbalanced fill - use table R404.1.1 (1-4).
· Clarify rebar location with 3" clear from footing bottom, R403.1.3.
· Locate and specify all anchor-bolt spacing on the foundation plan. Minimum ½" diameter with 7" embedment into concrete or masonry. Maximum spacing 6' o/c and within 12" of each sill plate end, R403.1.6.
· Specify and locate all foundation hold-downs and anchor-bolt spacing (at quarter points) for brace wall panels, R403.1.6 & R602.10.3 or R602.10.6.
· Epoxy connections require special inspections. If used, a special inspection request must be included with the permit application.

FLOOR PLANS:

· Note that tub/shower enclosures shall have nonabsorbent surfaces to 6' above the floor, R307.2. All glass enclosures shall be tempered, R308.4.5.
· Show fireplace location, hearth size and materials, R1003.10 or R1004.2. Provide fireplace cut sheets, make, model number and the approval number of the UL-127 testing agency (IE: ICBO #) for factory built (zero clearance) fireplaces, R1002, or note the requirement for deferred submittal to building inspector at installation. Include a cross-section for masonry fireplaces showing compliance with R1003.

STRUCTURAL PLANS:

· Specify design criteria on plans. Provide values for floor dead load and live load as well as roof dead load and live load.
· Locate and identify brace wall panel materials (min 3/8" OSB) and locations along with the appropriate nailing schedule (8d @ 6" o/c edge & @12" o/c field), R602.10.6.
· Show details for typical non-bearing interior wall conditions (floor and rafter/joist connections & gaps).

ELEVATIONS:

· Calculate the attic space ventilation area using the correct attic area in compliance with R806.2. Note size and location of all vents needed to comply. (Provide by separated calculations for master bedroom, closet & bath, laundry.)
· Roof shingles may be used on roof slopes of 2:12 or greater R905.2.2. Select a roof system that complies with R905.
· Note and specify all roof slopes appropriate with selected material. (minimum allowable roof slope is ¼" per foot, R905.11.1)
· Note and dimension the fireplace chimney. Show a minimum 2' termination above any roof point within 10' measured horizontally, and not less than 3' above the point where the chimney passes through the roof, R1001.6.

SECTIONS - DETAILS - MISC. NOTES:

· Note and specify the size, spacing and length of anchor bolts for sill plates, top plates and ledgers, R403.1.6.
· Provide a header schedule consistent with Table 502.5(1).
· Show the ceiling gypsum board as either 5/8" or ½" sag resistant when applied to 24" o/c framing, IRC table R702.3.5 footnote d.
· Calculate the attic ventilation area using the correct attic area in compliance with R806.2. Note only 80% of the required ventilating area may be provided by ridge or gable vents when applying the reduced area calculation. Show the amount of eave vents needed to comply.
· Provide attic ventilation calculation for all concealed attic spaces and concealed rafter spaces, include required and provide net free ventilation area. Also, indicate the type, size and location of attic ventilation. Where eave or cornice vents are installed insulation shall not block the free flow or air. A minimum of 1-inch space shall be provided between the insulation and the roof sheathing at the location of he vent.

· Provide fire blocking between chimney chase and attic area, R1001.16.
· Show chimney crickets, R1001.17.

PLUMBING PLANS:

· The City of Tucson has adopted the 2003 Uniform Plumbing Code with state amendments (ARIZONA STATE PLUMBING CODE). The plans should reference this code.
· Note and specify all piping materials.
· Provide an isometric drawing of waste lines showing the size of waste lines, vents and required clean-outs.
· Provide the length of gas line (total developed length) from meter to the most remote appliance on the system and size the supply pipe for the connected demand, UPC 1217.2.
· Provide the total fixture unit demand for the entire property per 2003 UPC Table 6-4, and determine the supply line diameter from Table 6-5 assuming 46 to 60 psi. A water line diameter of 1" is usually required for a two-bathroom residence.
· Show plumbing vents (VTR) within acceptable distances from traps (maximum 6' for water closets), UPC Table 10-1.
· Plumbing vents shall be a minimum of 10 feet away from all air intakes, UPC 906.2.

MECHANICAL PLANS:

· Note on plans: Mechanical shall comply with 2003 IRC chapters 12 - 24.
· Provide a heated air source to all habitable rooms, R303.8.
· Show bathroom exhaust fan locations with CFM rating R303.3 and M1506.
· Gas appliances shall comply with ARIZONA STATE PLUMBING CODE combustion air requirements or Chapter 17, 2003 IRC. Show compliance for all appliances.
· Size the return air ducts and registers, IRC sections M1602 (heat pump or air conditioner - 6 sq. in. / 1000 BTU, M1403.1) (1ton cooling = 12,000 BTU).
· Provide an equipment specification list including the furnace and evap cooler.
· Show dryer vent size and location, M1501.
· Air intake openings shall be located a minimum of 10' from (any street or alley), or 2 feet below any vent or chimney, R303.4.

ELECTRICAL PLANS:

· Provide an exterior outlet at grade level located at both the front and back of the dwelling, E3801.7. These outlets shall be GFCI protected E3802.3. or show existings outlet for compliance of this section.
· Note that at least one 20 AMP branch circuit shall be installed to serve the laundry room and this circuit shall have no other outlets, E3603.3 and 3801.8.
16. Provide a note indicating only approved outlet boxes shall be used for ceiling fans, E4001.6.
· An arc-fault circuit interrupter shall protect bedroom outlets including receptacles, lights and smoke detectors, E3802.11.

INTERNATIONAL ENERGY CONSERVATION CODE:

· Show compliance.
The simplified prescribed energy values for glazing U=0.65, ceiling R=30 and walls R=13 complies with energy requirements 2003 IECC w/ local amendments. Show these values as well as the solar heat gain coefficient SHGC minimum value of 0.40 rather than the previously accepted MEC values. R-30 batt insulation will not provide rated value in a 2" x 8" space
· Provide energy calculations per the 2003 IECC w/ local amendments (climate zone 4B, Pima County < 4000 ft, 2100 HDD) to support selected "R" values of insulation and "U" values of the windows and doors.
the simplified prescribed energy values for glazing U=0.65, ceiling R=30 and walls R=13 http://www.energycodes.gov/rescheck/
· Show the "R" values of insulation, as well as the "U" values of the windows and doors on the plans as well as the solar heat gain coefficient SHGC minimum value of 0.40 rather than the previously accepted MEC values.

If you have any questions, please contact your assigned plans examiner Adrian Alegria at 791-5550, extension 1186.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/10/2006 GERARDO BONILLA OUT TO CUSTOMER Completed
08/10/2006 SUE REEVES REJECT SHELF Completed