Permit Number: T06CM03944
Parcel: 11516025C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM03944
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/05/2006 PATRICIA GILBERT ENGINEERING REVIEW Approved
07/07/2006 MARTIN BROWN FIRE REVIEW Approved
07/07/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how the testing room is to be heated. reference Section 309.1, IMC 2003.
2. When the evaporative cooler is not being used, how is the space being ventilated and how much ventilation is to be provided. Reference Section 403, IMC 2003.
3. Provide a cut sheet for AC-1.
07/07/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
07/07/2006 ROBERT SHERRY WATER REVIEW Approved
07/07/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
07/07/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/11/2006 HEATHER THRALL ZONING REVIEW Approved
07/14/2006 DROBEY1 WWM REVIEW Needs Review
07/14/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review