Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM03944
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/05/2006 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
07/07/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
07/07/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show how the testing room is to be heated. reference Section 309.1, IMC 2003. 2. When the evaporative cooler is not being used, how is the space being ventilated and how much ventilation is to be provided. Reference Section 403, IMC 2003. 3. Provide a cut sheet for AC-1. |
07/07/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
07/07/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
07/07/2006 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
07/07/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
07/11/2006 | HEATHER THRALL | ZONING | REVIEW | Approved | |
07/14/2006 | DROBEY1 | WWM | REVIEW | Needs Review | |
07/14/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |