Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM03913
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/03/2006 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 07/03/2006 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 07/05/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1) PROVIDE ARIZONA SEAL ACCORDING TO ARIZONA STANDARD |
| 07/05/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The minimum acceptable font sze is 1/8" (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 2. All mechanical work is to be part of this permit (see sheet A-2.0). 3. Specify the minimum resistance (R-value) of the duct insulation to be used for new ducts on this project. Reference Section 803.2.8, IECC 2003. 4. Clarify what changes are to be made to the HVAC unit (see keynote 6, Sheet M-2). |
| 07/05/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE ARIZONA SEAL ACCORDING TO ARIZONA STANDARD 2) DESIGNATE / LOCATE WALL SECTION ON FLOOR PLAN. 3) PROVIDE ACCESSIBLE PATH INTO STOCK ROOM 4) HVAC NEED TO BE PERMITED. CANNOT BE UNDER SEPARATE PERMIT. 5) CLARIFY / SPECIFY MILLWORK AND ACCESSIBILITY REQUIREMENTS. LOCATE MILLWORK ON DRAWINGS. 6)DESIGNATE LOCATION OF SOFFIT. |
| 07/05/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/05/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 07/05/2006 | RSHERRY1 | WWM | REVIEW | Passed | |
| 07/05/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/18/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |