Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T06CM03878
Parcel: 11449040P

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T06CM03878
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/24/2006 LINHART PETERSEN POERS ASSOC. 2ND PARTY REVIEW REVIEW Denied November 21, 2006 CITY OF TUCSON - FIRST CHECK
Tucson Appl. No. T06CM03878
Bureau Veritas Job No. 01006-161082
Ms. Barb McNaughton
2750 N. Pantano Road
Tucson, Arizona 857151



Re: Plan Review: McNaughton Detached Barn
Address: 2570 N. Pantano Rd

Dear Ms. McNaughton:

Bureau Veritas North America has completed a review of the following documents on behalf of the City of Tucson:

Plans: Two (2) copies of plans (1 sheet) no dates, no stamps.

Structural Calculations: Two (2) copies of structural calculations and trusses, no dates no wet seals.

Soils Letter/Report: None submitted with this review.

Energy Compliance: None submitted with this review.


These documents were reviewed only for their conformance to the provisions of the 2003 International Building Codes (i.e., State of Arizona and Tucson amended 2003 IRC, 2003 IMC, 2002 NEC and 2003 IPC).

Please submit an itemized response letter and required number of complete and revised documents with all revisions clouded.



Sincerely,

BUREAU VERITAS NORTH AMERICA



Shelley Knuffke
ICC Plans Examiner






SK:pc F:\Tucson\01006-1610082pc1.doc
enclosures




McNaughton Detached Barn City of Tucson - First Check
2750 N. Bantano Rd Bureau Veritas Job No.:01006-161082
November 21, 2006 Page


A. The following plan review comments are based on the City of Tucson Building Regulations and referred to the 2003 International Residential Code.

B. Please respond in writing to each comment by marking the attached comment list or creating a response letter. Indicate which detail, specification, or calculation shows the requested information. Your complete and clear responses will expedite the re-check and hopefully, approval of this project. Thank you for your assistance.

C. These plan review comments are based on building code items only. If site-related comments are applicable to this project, they will be generated by others (e.g., County Engineering, Public Works, Health, etc.).

GENERAL COMMENTS:

Engineer’s wet seal must be provided on all structural calculations.

Provide electrical plan: including wire sizing, panel schedule, trench depth, etc.


If you have any questions regarding the above comments, please contact Shelley Knuffke at (520) 576-8400 between 8:00 A.M. to 5:00 P.M., M-F.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/22/2006 FSANCHE1 OUT TO CUSTOMER Completed